- š”ļø 3-Phase SYN/ASY Synchronous & Asynchronous Adjustable Voltage & Current Protection Relay
- š¦ Work Modes:
- Synchronous (SYN): Three-phase relays open and close simultaneously.
- Asynchronous (ASY): Three-phase relays operate independently.
- ā” Applications: Protects three-phase systems from over-voltage, under-voltage, over-current, phase imbalance, and phase sequence faults.
- š Installation: 35mm DIN Rail
š§ Key Protection Features:
- ā” Over-voltage Protection:
- Protection Value (U1): Adjustable range: 230Vā300V
- Recovery Value (U2): Adjustable range: 220Vā295V
- Action Time (U4): Adjustable range: 0.1sā30s
- Recovery Delay Time (U3): Adjustable range: 1sā500s
- ā ļø Under-voltage Protection:
- Protection Value (U5): Adjustable range: 140Vā210V
- Recovery Value (U6): Adjustable range: 145Vā215V
- Action Time (U8): Adjustable range: 0.1sā30s
- Recovery Delay Time (U7): Adjustable range: 1sā500s
- š„ Over-current Protection:
- Protection Value (C1): Adjustable range: 1Aā63A / 1Aā100A / OFF
- Recovery Delay Time (C2): Adjustable range: 1sā500s
- Action Time (C3): Adjustable range: 0.1sā30s
- Continuous Over-current Times (C5): Adjustable range: 1ā20 / OFF
- š Three-Phase Unbalance Protection:
- Unbalance Value (U10): Adjustable range: 20Vā99V
- Recovery Value (U11): Adjustable range: 15Vā94V
- š Phase Sequence Protection (U12): ON/OFF
āļø Adjustable Parameters:
- ā±ļø Power-on Delay Time (P1): Adjustable range: 1sā500s
- š ļø Voltage Calibration (U9): ±9.5% adjustable
- š Current Calibration (C4): ±9.5% adjustable
- š Synchronization Mode (CEL): ASY/SYN
š Monitoring & Calibration:
- š Voltage Display: Real-time voltage monitoring for all three phases.
- š Current Display: Real-time current monitoring for all three phases.
- š ļø Manual Calibration: Allows fine-tuning of voltage and current measurements for accuracy.
š” Ideal For:
- Protecting three-phase industrial equipment such as motors, pumps, air conditioners, and other high-power devices.
- Ensuring safe and stable operation of three-phase electrical systems during voltage fluctuations, phase imbalances, and current surges.
š Important Notes:
- ā³ Initial Setup: Ensure proper wiring and configuration before use. Adjust parameters according to system requirements.
- š Mode Selection: Choose between synchronous (SYN) or asynchronous (ASY) modes based on the application.