š”ļø 3-Phase DIN Rail Voltage Monitoring & Sequence
- Protection Relay
- š¦ Model: TVPS3-8A
- ā” Rated Voltage: 380VAC (Operating Range: 300ā490VAC)
- š Installation: 35mm DIN Rail
- āļø Dimensions: 80mm x 54mm x 44mm
- š” Weight: 128g
š§ Key Features:
- ā” Microprocessor Technology: Provides highly accurate and repeatable protection with a measurement error of less than 1%.
- š„ļø Built-in LCD & Keypad: Allows precise digital settings for voltage thresholds and delay times.
- š Adjustable Protection Parameters:
- Over-voltage Threshold: Adjustable within the operating range.
- Under-voltage Threshold: Adjustable within the operating range.
- Phase Unbalance Threshold: Adjustable with a hysteresis of 2%.
- ā±ļø Independent Delay Times: Adjustable for over-voltage, under-voltage, and phase unbalance protection.
- š Reset Method: Configurable as either automatic reset (5s) or manual reset.
- š Failure Recording: Stores the last three fault events for diagnostics.
āļø Protective Functions:
- ā ļø Phase Loss (Failure): Tripping time: 1 second.
- š Phase Sequence (Reversal): Instantaneous tripping.
- š Phase Unbalance (Asymmetry): Detects and protects against phase imbalance with adjustable thresholds.
- ā” Over-voltage Protection: Protects against excessive voltage levels.
- ā ļø Under-voltage Protection: Safeguards against low voltage conditions.
š Technical Specifications:
- š Voltage Hysteresis: 10V
- š Output Type: 1 NO (Normally Open) & 1 NC (Normally Closed) contacts.
- ā” Contact Capacity: 6A, 250VAC / 30VDC (Resistive Load).
- š Degree of Protection: IP20
- š”ļø Working Conditions: -25°C to 65°C, <85% RH non-condensing.
- ā³ Mechanical Durability: 1,000,000 cycles.
- š”ļø Dielectric Strength: >2kV AC for 1 minute.
š” Applications:
- Ideal for protecting industrial equipment such as:
- Pumps, Fans, Refrigeration Units, Blowers, Motors, Compressors.
- Lifts, Elevators, Cranes, Mining Excavators, and Conveyors.
- Ensures safe and reliable operation in environments with fluctuating voltages, phase imbalances, or sequence issues.
š Important Notes:
- ā³ Initial Setup: Ensure proper wiring and configuration before use. Adjust thresholds and delay times according to system requirements.
- š Reset Configuration: Choose between automatic or manual reset based on application needs.





















Reviews